Skip to content

Circular mils and maximum distance, by wire size and current

NEC Voltage Drop Chart

This page collects the reference numbers behind the voltage drop calculator into chart form: circular mils by wire size straight from NEC Chapter 9, Table 8, plus a maximum one-way distance table for common copper branch-circuit currents that keeps the drop under the NEC-recommended 3% at 120V and 240V. Use the calculator for your exact numbers, use this chart to compare wire sizes and distances at a glance.

AWG and kcmil to circular mils chart

Circular mils (CM) describe a conductor's cross-sectional area. These are the exact NEC Chapter 9, Table 8 values (not the AWG-diameter approximation formula), the same table this site's voltage drop calculator uses internally.

Wire sizeCircular mils (CM)
14 AWG4,107
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
3 AWG52,620
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600
250 kcmil250,000
300 kcmil300,000
350 kcmil350,000
400 kcmil400,000
500 kcmil500,000
600 kcmil600,000
750 kcmil750,000
1000 kcmil1,000,000

Maximum one-way distance for 3% drop, 120V single-phase, copper

These figures are calculated with the same formula as the calculator (VD = 2 × K × I × L ÷ CM, K = 12.9 for copper), solved for the maximum one-way length L that keeps the drop at or under 3% of a 120V supply. Cells marked with a dash are current levels not typically paired with that wire size on a standard branch-circuit breaker (small-conductor overcurrent limits), they are left out to avoid implying a combination that would not be code-compliant regardless of voltage drop. Actual code-required ampacity depends on insulation rating and installation method and is a separate question from voltage drop, always confirm ampacity separately.

Wire size15A20A30A40A
14 AWG38 ftn/an/an/a
12 AWG61 ft46 ftn/an/a
10 AWG97 ft72 ft48 ftn/a
8 AWG154 ft115 ft77 ft58 ft
6 AWG244 ft183 ft122 ft92 ft

At 240V, the same wire size and current combination allows roughly double the distance above, because the same volts-dropped is a smaller percentage of a larger supply voltage. This is the same relationship covered in the calculator's "why supply voltage matters" logic.

How to read this chart

Pick the row for your wire size and the column closest to your load current, the distance shown is the farthest you can run that wire, one-way, before the drop reaches 3% at 120V. If your actual run is longer than the listed distance, either move up a wire size (a lower AWG number) or expect a drop above 3%, which may still be acceptable depending on the rest of the circuit, this is exactly what the voltage drop calculator works out precisely for your own current, distance, wire size, material and supply voltage rather than the fixed steps in this chart. See the voltage drop formula page for exactly how each distance in the table above was derived, including the algebra rearranged to solve for distance directly.

DC and low-voltage charts (12V, 24V)

Low-voltage DC systems, landscape lighting transformers, solar battery banks, RV and marine 12V circuits, are the case where this chart matters most in relative terms, because a few tenths of a volt of drop can already be a meaningful percentage of a 12V or 24V supply. The formula is identical (DC uses the same 2 × K × I × L ÷ CM single-phase-style formula), only the supply voltage changes, which is why a fixed chart at one voltage does not generalize well to 12V work, run your exact current and distance through the calculator instead of scaling a 120V chart by hand.

Why a fixed chart has limits

Any printed chart, including this one, has to fix most variables to fit on a page: one supply voltage, one conductor material, a handful of current steps. Real jobs rarely land exactly on a chart row. A run at 22A instead of 20A, a supply voltage of 208V instead of 120V or 240V, or an aluminum feeder instead of copper, all fall between the lines of a fixed table like this one. The calculator does not have that limitation, since it computes the exact voltage drop and percentage for whatever current, distance, wire size, material, circuit type and supply voltage you actually have, rather than rounding to the nearest chart row, entirely in your browser, see the privacy policy for details. Treat this chart as a fast sanity check or a way to compare a few wire sizes side by side, and use the calculator for the number you actually rely on.

Frequently asked questions

Where do these circular mil numbers come from?
They are the published values from NEC Chapter 9, Table 8, the standard reference table for conductor properties used throughout the electrical trade, not an approximation formula.
Does this chart account for wire insulation temperature rating?
No, the voltage drop numbers in this chart depend only on conductor material and circular-mil area, not insulation type. Ampacity limits (how much current a wire is rated to carry safely) do depend on insulation temperature rating and installation method, that is a separate table from NEC Chapter 3, not covered on this page.
Why does the maximum distance roughly double at 240V compared to 120V?
Voltage drop in volts for a given current, wire size and length does not change with supply voltage, but that same number of volts is a smaller percentage of a larger supply. Since the 3% target is a percentage, doubling the supply voltage roughly doubles the distance you can run before hitting 3%.
Can I use this chart for aluminum wire?
The 120V distance table above is for copper only, aluminum has a higher resistivity constant (K = 21.2 versus copper's 12.9), so an aluminum conductor drops more voltage at the same size and length. Use the calculator and switch the material toggle to aluminum for accurate aluminum figures.

Get your exact numbers

This chart uses fixed steps, the calculator works out your precise current, distance and wire size.

Go to the voltage drop calculator

Free. No sign-up.